For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 15.12.280 — Addition - 903.3.5.3 - Hydraulically calculated systems

Corona, California, Municipal Code (2026 S-57: Local legislation passed through Ord. 3427, passed 4-1-2026) · Corona Municipal Code § 15.12.280

Corpus is an independent public-information project, not the official City of Corona website. Stable reference: corpuslaw.us/code/cdf6415a-f483-42a6-9c1f-f683f4993c3d

15.12.280 Addition - 903.3.5.3 - Hydraulically calculated systems.

Section 903.3.5.3 is hereby added to read as follows: "903.3.5.3 Hydraulically calculated systems. The design of hydraulically calculated fire sprinkler systems shall not exceed 90% of the water supply capacity. Exception: When static pressure exceeds 100 psi and required by the Fire Code Official, the fire sprinkler system shall not exceed water supply capacity specified by Table 903.3.5.3. TABLE 903.3.5.3 Hydraulically Calculated Systems Design % [image omitted; see the official code] (Ord. 3421 § 10 (part), 2025; Ord. 3357 § 10 (part), 2022; Ord. 3306 § 11 (part), 2019.)

Ask a question about Corona law

Corpus searches the Corona sections it holds and shows the ones that match, with their citations. Free, no sign-in.