15.12.280 Addition - 903.3.5.3 - Hydraulically calculated systems.
Section 903.3.5.3 is hereby added to read as follows: "903.3.5.3 Hydraulically calculated systems. The design of hydraulically calculated fire sprinkler systems shall not exceed 90% of the water supply capacity. Exception: When static pressure exceeds 100 psi and required by the Fire Code Official, the fire sprinkler system shall not exceed water supply capacity specified by Table 903.3.5.3. TABLE 903.3.5.3 Hydraulically Calculated Systems Design % [image omitted; see the official code] (Ord. 3421 § 10 (part), 2025; Ord. 3357 § 10 (part), 2022; Ord. 3306 § 11 (part), 2019.)