15.12.370 Amendment - Tables B105.1(1), B105.1(2) and B105.2 of Appendix B -Minimum required fire flow and flow duration for buildings.
Tables B 105.1(1), B105.1(2) and B105.2 of Appendix B are deleted in their entirety and replaced with the following: "TABLE B105.l MINIMUM REQUIRED FIRE-FLOW AND FLOW DURATION FOR BUILDINGS* Use | Required Flow (gallons per minute) | Duration One- and Two-Family Dwelling | 1500 gpm | 2 hours Multi-Family Dwelling | 2500 gpm | 2 hours Commercial | 3000 gpm | 3 hours Industrial | 3500 gpm | 4 hours *Or as otherwise required by the Fire code official. *For fire flow requirements in a fire hazard severity zone, refer to the current adopted California Wildland-Urban Interface Code and Corona Municipal Code Chapter 15.25 Wildland-Urban Interface Code." (Ord. 3421 § 10 (part), 2025; Ord. 3357 § 10 (part), 2022; Ord. 3306 § 11 (part), 2019.)