15.12.380 Amendment - Table C102.1 of Appendix C - Number and spacing of fire hydrants.
Table C102.1 of Appendix C is amended in its entirety to read as follows: "TABLE C102.1 NUMBER AND SPACING OF FIRE HYDRANTS" Use | Maximum Distance Between Hydrants (feet) | Maximum Distance From Any Point on Street or Road Frontage or Fire Department Access to a Hydrant (feet) One- and Two-Family Dwelling | 300 | 150 Multi-Family Dwelling | 250 | 125 Commercial/Industrial | 250 | 125 (Ord. 3421 § 10 (part), 2025; Ord. 3357 § 10 (part), 2022; Ord. 3306 § 11 (part), 2019.)