§ 8.20.160 — COMMERCIAL HOOD AND DUCT SYSTEMS
Menifee Municipal Code (2026 S-15) · Menifee Municipal Code § 8.20.160
Corpus is an independent public-information project, not the official City of Menifee website. Stable reference: corpuslaw.us/code/13a3a5c8-52f3-4297-9d53-33bafae0514f
§ 8.20.160 COMMERCIAL HOOD AND DUCT SYSTEMS.
A new Section 904.2.2.1 is added to Section 904.2.2 of the California Fire Code to read as follows: 904.2.2.1 Activation of the Fire Alarm System. Where a fire alarm signaling system, or a Dedicated Function Fire Alarm System is serving the occupancy where the extinguishing system is located, the actuation of the automatic fire-extinguishing system shall actuate the fire alarm signaling system in accordance with the requirements of NFPA 72. If a fire alarm signaling system, or a Dedicated Function Fire Alarm System is not present, one will be required to be installed to provide monitoring for the automatic fire-extinguishing system. (Ord. 2025-425, passed 11-19-2025)