§ 8.20.220 TABLE B105.2.
Table B105.2 of the California Fire Code is amended as follows: REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES AUTOMAT IC SPRINKLE R SYSTEM (Design Standard) | MINIMUM FIRE FLOW (gallons per minute) | FLOW DURATION (hours) No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) Section 903.3.1.1 of the California Fire Code | 50% of the value in Table B105.1(2)a | Duration in Table B105.1(2) at the reduced flow rate Section 903.3.1.2 of the California Fire Code | 50% of the value in Table B105.1(2)b | Duration in Table B105.1(2) at the reduced flow rate For SI: 1 gallon per minute= 3.785 L/m a. The reduced fire-flow shall not be less than 1,000 gallons per minute. b. The reduced fire-flow shall not be less than 1,5000 gallons per minute. (Ord. 2022-364, passed 11-16-2022; Am. Ord. 2025-425, passed 11-19-2025)