15.24.440 Section 903.4 Amended - Sprinkler system supervision and alarms.
Section 903.4 Amended - Sprinkler System Supervision and Alarms, is hereby amended by modifying item 2, deleting items 5 and 8, and renumbering the exceptions as follows: Exceptions: 1. Automatic sprinkler systems protecting one- and two-family dwellings. 2. Limited area systems serving fewer than 20 sprinklers. 3. Automatic sprinkler systems are installed in accordance with NFPA 13R where the common supply main is used to supply both the domestic and automatic sprinkler system, and a separate shutoff valve for the automatic sprinkler system is not provided. 4. Jockey pump control valves that are sealed or locked in the open position. 5. Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position. 6. Trim valves to pressure switches in dry, pre-action, and deluge sprinkler systems that are sealed or locked in the open position. (Ord. 626-25 § 1 (part), 2025; Ord. 584 § 1, 2022)