15.24.450 Section 907.1.6 Added - Fire alarm control panel (FACP).

The main fire alarm control panel shall be located in the same room as and share the same access as the fire sprinkler riser. The FACP shall have a minimum of 36 inches of face clearance and 6 inches of side clearance from any other wall or equipment. (Ord. 626-25 § 1 (part), 2025; Ord. 584 § 1, 2022)