For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 15.24.490 — Section 914.12.2 Added - Automatic Fire Sprinkler Systems and Standpipes

Murrieta Municipal Code (2026 S-23 through Ord. 639-26) · Murrieta Municipal Code § 15.24.490

Corpus is an independent public-information project, not the official City of Murrieta website. Stable reference: corpuslaw.us/code/9744d7a0-beb8-4b24-bdb1-7c74294c62a5

15.24.490 Section 914.12.2 Added - Automatic Fire Sprinkler Systems and Standpipes.

Mid-rise buildings shall be protected throughout by an automatic fire sprinkler system designed and installed in conformance with the latest edition of NFPA 13 and in accordance with the following: 1. A shut-off valve and a water flow alarm shall be provided for each floor. Each shut-off valve and water flow alarm shall be electronically supervised. 2. Mid-rise buildings shall be provided with a Class I standpipe system that is interconnected with the automatic fire sprinkler system. The system shall consist of 2.5-inch hose valves located in each stair enclosure on every floor. Two hose outlets shall be located on the roof outside of each stair enclosure that penetrates the roof. The standpipe system shall be designed, installed, and tested in accordance with the latest edition of NFPA 14. 3. Fire department standpipe connections and valves serving each floor shall be located in the vestibule and located in a manner so as not to obstruct egress when hose lines are connected and charged. (Ord. 626-25 § 1 (part), 2025)

Ask a question about Murrieta law

Corpus searches the Murrieta sections it holds and shows the ones that match, with their citations. Free, no sign-in.