§ 15.04.3.3020 — CEC Article 230.28 amended
Oakland Municipal Code (Supp. No. 103: codified through Ordinance No. 13873, adopted February 17, 2026) · Oakland Municipal Code § 15.04.3.3020
Corpus is an independent public-information project, not the official City of Oakland website. Stable reference: corpuslaw.us/code/377136ac-12ba-4db2-b33a-548030825397
15.04.3.3020 - CEC Article 230.28 amended.
In Article 230.28 of the California Electrical Code, add the following new paragraph: "Conduit for overhead service conductors shall be rigid metal conduit or intermediate metal conduit not less than one and one-quarter (1.25) inch trade size. Aluminum rigid metal conduit shall be not smaller than two (2) inches trade size where used as a periscope."
(Ord. No. 13861, § 4, 9-15-2025)