15.04.3.3025 - CEC Article 230.29 amended.
In Article 230.29 of the California Electrical Code, add the following new paragraph: "Service conduit above a building or structure roof shall not extend more than thirty (30) inches beyond the last support without bracing. The outer or upper end of overhead service conduit shall extend horizontally not more than eighteen (18) inches beyond the point of support or fastening. Service conduit coupled above a structure or past the edge of same shall be braced or supported between the coupling and the point of attachment."
(Ord. No. 13861, § 4, 9-15-2025)