15.04.3.3030 - CEC Article 230.43.
In Article 230.43 of the California Electrical Code, replace the section in its entirety with the following: "Service entrance conductors shall be installed in approved rigid metal conduit or intermediate metal conduit on the outside of buildings or structures. Rigid non-metallic conduit (schedule 80) shall be permitted to be installed for underground service lateral conductors outside the building where exposed to physical damage. Rigid non-metallic conduit (schedule 40) shall be permitted to be installed for underground service lateral conductors where not exposed to physical damage outside the building. Termination cans or any equipment for service lateral conductors shall not encroach into the public way."
(Ord. No. 13861, § 4, 9-15-2025)