§ 6-8.826 — Pressure and leakage testing
City of Ontario, California, Municipal Code (2026 S-32: Current through Ordinance 3338, passed 7-21-2026) · Ontario Municipal Code § 6-8.826
Corpus is an independent public-information project, not the official City of Ontario website. Stable reference: corpuslaw.us/code/696c304c-b32f-4f4e-aa96-e15aac904880
Sec. 6-8.826. Pressure and leakage testing.
(a) A minimum four (4)-hour hydrostatic pressure test shall be performed and successfully completed in accordance with AWWA C600 or C605. (b) The contractor shall apply test pressures at an approved outlet or fitting located within five (5) feet vertically of the lowest point of each pipe section to be tested and securely plug such fittings. Where air valves or other suitable outlets are unavailable, the contractor shall provide approved taps and fittings for air release, and securely plug these. (c) Flushing of mains with water at a velocity of at least two and one-half (2.5) feet per second over its entire length shall be performed using an eccentric reducer. Velocity through outlets and fittings shall not exceed twenty five (25) feet per second during flushing. (d) Leakage shall be computed as the total quantity of water pumped into the pipeline during the test period, including water added to reach the specified test pressure for the final time. Leakage shall not exceed the rate specified for the type of pipe tested. The contractor shall repeat the testing until the leakage does not exceed the specified leakage rate. The contractor shall repair all visible leaks regardless of the amount of leakage at their sole expense. All tests shall be completed in the presence of the City Inspector who shall record the results. (§ 4, Ord. 3297, eff. March 18, 2025)
Ask a question about Ontario law
Corpus searches the Ontario sections it holds and shows the ones that match, with their citations. Free, no sign-in.