§ 16.52.508 — Fire command center

Code of Ordinances, City of Sunnyvale, California (includes legislation through Ord. No. 3260-26 adopted August 11, 2026) · Sunnyvale Code of Ordinances § 16.52.508

Corpus is an independent public-information project, not the official City of Sunnyvale website. Stable reference: corpuslaw.us/code/cbc953d7-7b94-41bb-84fe-579948ef0c08

§ 16.52.508: Fire command center.

(a) Location and access. California Fire Code Section 508.1.1 is hereby amended to read: 508.1.1 Location and access. The location and access of the fire command center shall be approved by the fire code official. The fire command center shall be located adjacent to an approved fire apparatus access road and be accessible directly from the exterior of the building. (b) Required features. California Fire Code Section 508.1.6 is hereby amended to read: 508.1.6 Required features. The fire command center shall comply with NFPA 72 and shall contain the following features: 1. The emergency voice/alarm communication system control unit. 2. The fire department communications system. 3. Fire alarm system zoning annunciator panel required by Section 907.6.4.3. 4. Annunciator unit visually indicating the location of the elevators and whether they are operational. 5. Status indicators and controls for air distribution systems. 6. The firefighter's control panel required by Section 909.16 for smoke control systems installed in the building. 7. Controls for unlocking interior exit stairway doors simultaneously. 8. Sprinkler valve and water-flow detector display panels. 9. Emergency and standby power status indicators. 10. A telephone for fire department use with controlled access to the public telephone system. 11. Fire pump status indicators. 12. Schematic building plans indicating the typical floor plan and detailing the building core, means of egress, fire protection systems, firefighter air-replenishment systems, firefighting equipment and fire department access, and the location of fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions. 13. An approved Building Information Card that contains, but is not limited to, the following information: 13.1 General building information that includes: property name, address, the number of floors in the building above and below grade, use and occupancy classification (for mixed uses, identify the different types of occupancies on each floor), estimated building population during the day, night and weekend; 13.2 Building emergency contact information that includes: a list of the building's emergency contacts, including, but not limited to, building manager, building engineer and their respective work phone number, cell phone number, and e-mail address; 13.3 Building construction information that includes: the type of building construction including, but not limited to, floors, walls, columns and roof assembly; 13.4 Exit stair information that includes: number of exit stairs in the building, each exit stair designation and floors served, location where each exit stair discharges, exit stairs that are pressurized, exit stairs provided with emergency lighting, each exit stair that allows reentry, exit stairs providing roof access; elevator information that includes: number of elevator banks, elevator bank designation, elevator car numbers and respective floors that they serve, location of elevator machine rooms, location of sky lobby, location of freight elevator banks; 13.5 Building services and system information that includes: location of mechanical rooms, location of building management system, location and capacity of all fuel oil tanks, location of emergency generator, location of natural gas service; 13.6 Fire protection system information that includes: locations of standpipes, location of fire pump room, location of fire department connections, location of firefighter air replenishment system features and stations, location of emergency responder radio system controller, floors protected by automatic sprinklers, location of different types of automatic sprinkler systems installed (e.g., dry, wet, pre-action, etc.); and 13.7 Hazardous material information that includes: location of hazardous material, quantity of hazardous material. 14. Work table and chairs. 15. Generator supervision devices, manual start and transfer features. 16. Public address system, where specifically required by other sections of this code. 17. Elevator fire recall switch in accordance with ASME A17.1. 18. Elevator emergency or standby power selector switch(es), where emergency or standby power is provided. 19. A master switch for unlocking elevator lobby doors permitted by Section 1010.2.12.1. 20. Building security system controls and related equipment. 21. All control panels shall be permanently identified in an approved manner as to function. 22. Other fire protection equipment and system controls as required by the fire code official. Fire command centers shall not be used for the housing of any boiler, heating unit, generator, combustible storage, or similar hazard. (c) Ventilation. California Fire Code Section 508.1.8 is hereby amended to read: 508.1.8 Ventilation. The fire command center shall be provided with an independent ventilation or air conditioning system in accordance with the California Mechanical Code and have manual shut-off capability within the fire command center.

( Ord. 3018-13 § 2 ; Ord. 3101-16 § 1 ; Ord. 3148-19 § 1 ; Ord. 3201-22 § 1 ; Ord. 3247-25 , 10/21/2025 )

Ask a question about Sunnyvale law

Corpus searches the Sunnyvale sections it holds and shows the ones that match, with their citations. Free, no sign-in.