(a) Anchor guys will be effectively grounded and will be electrically continuous to earth through the anchor. Therefore, these guys shall not be broken with strain insulators. A guy bond clamp will be inserted in all bolt and nut thimbleeyes, except at pole-to-pole guys, where ground continuity is not dependent upon the pole-to-pole guy. (b) If the strand at dead ends is not effectively earth-grounded, it will be so grounded by a length of No. six solid bare copper wire bonded to the messenger with compression ground clamps and the copper wire bonded to a ground rod driven its full length (and six inches below the surface) into the earth. (c) All equipment cabinets, cans, fused cutout cabinets, metal meter socket bases, etc., will be grounded through a length of No. six solid bare copper wire bonded to a minimum eight foot ground rod driven to its full length (and six inches below the surface) into the earth.