§ 23-248 — Cross-connection control programs: Requirements

Municipal Code of the City of West Covina, California (Codified through Ordinance No. 2531, adopted July 15, 2025. (Supp. No. 94)) · West Covina Municipal Code § 23-248

Corpus is an independent public-information project, not the official City of West Covina website. Stable reference: corpuslaw.us/code/cc69c345-2c74-4ad4-89dd-ee68175d0810

Sec. 23-248. - Cross-connection control programs: Requirements.

(a) No water service connection to any premises shall be installed or maintained by the city unless the water supply is protected as required by state laws and regulations and these sections. Service of water to any premises shall be discontinued by the water purveyor if a backflow prevention device required by this section is not installed, tested and maintained, or if it is found that a backflow prevention device has been removed, bypassed or if an unprotected cross-connection exists on the premises. Service will not be restored until such conditions or defects are corrected. (b) The customer's system shall be open for inspection at all reasonable times to authorized representatives of the director of public works to determine whether cross-connections or other structural or sanitary hazards, including violations of these sections, exist. When such a condition becomes known, the director of public works shall deny or immediately discontinue service to the premises by providing for a physical break in the service line until the customer has corrected the condition(s) in conformance with all state and city requirements. (c) An approved backflow prevention device shall also be installed on each service line to a customer's system in all cases, before the first branch line leading off the service line wherever the following conditions exist: (1) In the case of premises having an auxiliary water supply which is not or may not be of safe bacteriological or chemical quality and which is not acceptable as an additional source by the director of public works, the public water system shall be protected against backflow from the premises by installing a backflow prevention device in the service line appropriate to the degree of hazard. (2) In the case of premises on which any industrial fluid or any other objectionable substance is handled in such a fashion as to create an actual or potential hazard to the public water system the public system shall be protected against backflow from the premises by installing a backflow prevention device in the service line appropriate to the degree of hazard. This shall include the handling of processed waters and waters originating from the utility systems which have been subject to deterioration in quality. (3) In the case of premises having (1) internal cross-connections that cannot be permanently corrected and controlled, or (2) intricate plumbing and piping arrangements or where entry to all portions of the premises is not readily accessible for inspection purposes making it impracticable or impossible to ascertain whether or not dangerous cross-connections exist, the public water system shall be protected against backflow from the premises by installing a backflow prevention device in the service line. (d) In the case of any premises where there is water or substance that would be objectionable but not hazardous to health, if introduced into the public water system, the public water system shall be protected by an approved double-check valve assembly. (e) In the case of any premises where there is any material dangerous to health which is handled in such a fashion as to create an actual or potential hazard to the public water system, the public water system shall be protected by an approved backflow prevention device approved by the City of West Covina and the state department of health services. Examples of premises where these conditions will exist include but are not limited to chemical manufacturing plants, hospitals, mortuaries and plating plants. (f) In the case of any premises where there are "uncontrolled" cross-connections, either actual or potential, the public water system shall be protected by an approved air-gap separation or an approved reduced pressure principle backflow prevention device at the service connection. (g) In the case of any premises where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete in-plant cross-connection survey, the public water system shall be protected against backpressure or back-siphonage from the premises by the installation of a backflow prevention device in the service line. In this case, maximum protection will be required: That is, an approved air-gap separation or an approved reduced pressure principle backflow prevention device shall be installed in each service to the premises. (h) In the case of premises with cross-connections to sewage lines, pumps, flushers, etc., the public water system shall be protected by an approved backflow prevention device approved by the City of West Covina and the state department of health services. Examples include sewage treatment plants and pumping stations. (i) In the case of tanker and spray tanks, an air-gap separation or an approved reduced pressure principle backflow prevention device is required. (j) The City of West Covina or the state department of health services may, at their discretion, require an industrial water user to designate a user supervisor when the water user's premises has a multipiping system that conveys various types of fluids, some of which may be hazardous and where changes in the piping system are frequently made. The user supervisor shall be responsible for the avoidance of cross-connections during the installation, operation and maintenance of the water user's pipelines and equipment. (k) All backflow preventors will be tested upon installation, relocation or when any repairs are made on the device. (l) The installation and location of the backflow device or devices shall be determined by the City of West Covina under the standards set out here.

(Ord. No. 1848, § 4, 6-25-90)

Ask a question about West Covina law

Corpus searches the West Covina sections it holds and shows the ones that match, with their citations. Free, no sign-in.