§ 23-268 — Design criteria
Municipal Code of the City of West Covina, California (Codified through Ordinance No. 2531, adopted July 15, 2025. (Supp. No. 94)) · West Covina Municipal Code § 23-268
Corpus is an independent public-information project, not the official City of West Covina website. Stable reference: corpuslaw.us/code/3fa25b35-cc3f-46bd-98e9-81f9ad340958
Sec. 23-268. - Design criteria.
(a) Consumption rates. The consumption rates for the design of the system shall be as follows: (1) Population based upon three and two-tenths (3.2) persons per household. (2) Average day consumption, two hundred thirty (230) gallons per capita. (3) Maximum day consumption, four hundred sixty (460) gallons per capita. (4) Peak hour rate, one (1) gallon per minute per person. (b) Fire flow. The fire flow requirements for this area shall be: Two thousand (2,000) gallons per minute for two (2) hours. The area to be served by a single fire hydrant is one hundred fifty thousand (150,000) square feet.
(Code 1960, § 7625; Ord. No. 1371, § 1, 2-27-78)
Ask a question about West Covina law
Corpus searches the West Covina sections it holds and shows the ones that match, with their citations. Free, no sign-in.
