§ 8-8009 — Out-of-service and abandoned storage systems

Code of Ordinances of the City of Savannah, Georgia (Division II) (enCodePlus online edition as published 2026-11-20) · Savannah Code of Ordinances, pt. 8, ch. 8., § 8-8009

Corpus is an independent public-information project, not the official City of Savannah website. Stable reference: corpuslaw.us/code/c907e20b-efd7-4bdf-acba-2bfacb70613c

Sec. 8-8009. - Out-of-service and abandoned storage systems.

(I) Out-of-service storage systems. (a) The owner or operator of out-of-service underground storage system shall have recorded an inventory at least once every 15 calendar days and shall examine and record results of the leak detection and monitoring system monthly unless the underground storage system contains no pollutant. An out-of-service storage system which contains no pollutant shall be secured against tampering and unauthorized filling and shall be inspected monthly for sign of damage to the security system. The underground storage system may be filled with water for ballasting. (b) An underground storage system may be kept out of service for more than one year and not deemed abandoned if approved by the fire marshal. (II) Abandoned storage systems. (a) The owner or operator of an underground storage system that is to be abandoned or is declared abandoned under the provisions of this chapter must, within 48 hours of abandonment, pump the system clean of pollutants. Within 90 days of abandonment, the owner or operator shall remove the underground storage system in a safe manner, except that in lieu of removal, the underground storage tanks may be filled with sand, concrete or other inert material in accordance with requirements in API bulletin 1604, 1981, chapter 2. (b) The owner or operator of an abandoned underground tank shall not dispose of such tank except in accordance with the specifications of API 1604, chapters 3 and 6, and the following requirements: If the tank is disposed of as junk, it must be rendered vapor free and dismantled or perforated in a safe manner so as to render it unfit for further use. (c) An abandoned underground storage system may be brought into service only if it has been completely retrofitted in compliance with the applicable requirements in section 8-8010. (d) No person shall place pollutants in an abandoned storage system.

(Code 1977, § 8-8009)

Ask a question about Savannah law

Corpus searches the Savannah sections it holds and shows the ones that match, with their citations. Free, no sign-in.