§ 3-11-8 — Water supply
Code of Ordinances of the City of Meridian, Idaho (Supp. No. 14: codified through Ordinance No. 26-2129, enacted July 7, 2026) · Meridian Code of Ordinances § 3-11-8
Corpus is an independent public-information project, not the official City of Meridian website. Stable reference: corpuslaw.us/code/6db62791-e37e-48d1-b32d-e669c06097a0
3-11-8. - Water supply.
A. General requirements. An accessible, adequate, safe and potable supply of water shall be provided in each mobile home park. Where a public supply of water of satisfactory quantity, quality, and pressure is available at the site or at the boundary of the site, connection shall be made thereto and its supply used exclusively. B. Source of supply. 1. Supply capacity. The water supply shall be capable of supplying a minimum of one hundred twenty-five (125) gallons per day per mobile home. 2. Free from contamination. Every well or suction line of the water supply system shall be located and constructed in such a manner that neither underground nor surface contamination will reach the water supply from any source. 3. Gravity drainage. No well-casings, pumping machinery or suction pipes shall be placed in any pit, room or space extending below ground level nor in any room or space above ground, which is walled in or otherwise enclosed, unless such rooms, whether above or below ground, have free drainage by gravity to the surface of the ground. 4. Private water supply. The treatment of a private water supply shall be in accordance with applicable laws and regulations. C. Water distribution system. 1. Connections through pipes. The water supply system of the mobile home park shall be connected by pipes to all mobile homes, buildings and other facilities requiring water. 2. Compliance with state and local regulations. All water piping, fixtures and other equipment shall be constructed and maintained in accordance with state and local regulations, approved by the City Council and shall be of a type and in locations approved by the city health authority. 3. Backflow protection. The water piping system shall not be connected with nonpotable or questionable water supplies and shall be protected against the hazards of backflow or back siphonage. 4. Size and pressure. The system shall be so designed and maintained as to provide a pressure of not less than twenty (20) pounds per square inch, under normal operating conditions at service buildings and other locations requiring potable water supply and be of the size required by the city. 5. Fire hydrants. Fire hydrants shall be required to maintain safe standards of fire protection, and shall be located not more than five hundred (500) feet from any trailer stand. D. Individual water riser pipes and connections. 1. Location. Individual water riser pipes shall be located within the confined area of the mobile home stand at a point where the water connection will approximate a vertical position. 2. Requirements. Water riser pipes shall extend at least four (4) inches above ground elevation. The pipe shall be at least three-fourths (¾) inch. The water outlet shall be capped when a mobile home does not occupy the lot. 3. Prevention of freezing of service lines. Adequate provisions shall be made to prevent freezing of service lines, valves and riser pipes and to protect risers from heaving and thawing actions of ground during freezing weather. Surface drainage shall be diverted from the location of the riser pipe. 4. Shutoff valve. A shutoff valve below the frost line shall be provided near the water riser pipe on each mobile home lot. E. Stop and waste valves. Underground stop and waste valves shall not be installed on any water service.
Ask a question about Meridian law
Corpus searches the Meridian sections it holds and shows the ones that match, with their citations. Free, no sign-in.