Sec. 29.5-3.12. - Protection by fill.

A building allowed to be protected from flooding by being constructed on permanent fill shall comply with the following: (a) The lowest floor (including basement) shall be at or above the flood protection elevation. (b) The fill shall be placed in layers no greater than one foot deep before compaction and should extend at least ten (10) feet beyond the foundation of the building before sloping below the flood protection elevation. The top of the fill shall be above the flood protection elevation. However, the ten-foot minimum may be waived if a structural engineer certifies an alternative method to protect the building from damages due to hydrostatic pressures. The fill shall be composed of rock or soil (sound structural fill materials) and not incorporate debris or refuse materials. The fill shall be protected against erosion and scour. The fill shall not adversely affect the flow or surface drainage from or onto neighboring properties.

(C.B. No. 97-265, § 1, 10-7-97)