§ 18-28-506.3.5 — Air velocity

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-506.3.5

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/3197953d-951e-4b36-b2ab-837709e1e0b2

18-28-506.3.5 Air velocity.

Grease duct systems serving a Type I hood shall be designed and installed to provide an air velocity within the duct system of not less than 1,500 feet per minute (7.6 m/s). Exception: The velocity limitations shall not apply within duct transitions utilized to connect ducts to differently sized or shaped openings in hoods and fans, provided that such transitions do not exceed 3 feet (914 mm) in length and are designed to prevent the trapping of grease.