For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18-28-506.3.7 — Clearances

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-506.3.7

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/512b21c8-a5c2-4021-95b1-be1ebe56bb6a

18-28-506.3.7 Clearances.

Grease duct systems serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm). Exception: Listed and labeled factory-built commercial kitchen grease ducts installed in accordance with the Chicago Fire Prevention Code. (Amend Coun. J. 9-14-21, p. 35949, Art. V, § 13)

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.