§ 18-28-506.3.7 — Clearances
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-506.3.7
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/512b21c8-a5c2-4021-95b1-be1ebe56bb6a
18-28-506.3.7 Clearances.
Grease duct systems serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm). Exception: Listed and labeled factory-built commercial kitchen grease ducts installed in accordance with the Chicago Fire Prevention Code. (Amend Coun. J. 9-14-21, p. 35949, Art. V, § 13)