§ 18-28-706.1 — Mechanical combustion air supply for oil-fired appliances

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-706.1

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/0ad7ed7c-2e19-4d07-9547-161a17dccbe1

18-28-706.1 Mechanical combustion air supply for oil-fired appliances.

Where all combustion air and dilution air is provided by a mechanical forced-air system, the combustion air and dilution air shall be supplied at the minimum rate of 1 cfm per 2,400 Btu/h [0.00067 m 3 /(s x kW)] of combined input rating of all the fuel-burning appliances served. Each of the appliances served shall be electrically interlocked to the mechanical forced-air system so as to prevent operation of the appliances when the mechanical system is not in operation. Where combustion air and dilution air is provided by the building's mechanical ventilation system, the system shall provide the specified combustion/dilution air rate in addition to the required ventilation air.