§ 18-28-709.2 — Dampered openings
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-709.2
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/828cd2c7-3d19-4be7-8063-be4d94950b01
18-28-709.2 Dampered openings.
Where the combusting air openings are provided with volume, smoke or fire dampers, the dampers shall be electrically interlocked with the firing cycle of the appliances served, so as to prevent operation of any appliance that draws combustion and dilution air from the room when any of the dampers are closed. Manually operated dampers shall not be installed in combustion air openings.
Ask a question about Chicago law
Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.
