For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18-29-605.5 — Water distribution pipe

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-605.5

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/ced3275b-4eed-471f-8d61-2a758b1fdb86

18-29-605.5 Water distribution pipe.

Water distribution pipe shall conform to NSF 61 and shall conform to one of the standards listed in Table 18-29-605.5. All hot water distribution pipe and tubing shall have a minimum pressure rating of 100 psi (690 kPa) at 180°F (82°C). (Amend Coun. J. 6-17-26, p. 45214, Art. IV, § 59) Table 18-29-605.5 Water Distribution Pipe Material | Standard Material | Standard Brass pipe | ASTM B43 Chlorinated Polyvinyl Chloride (CPVC) plastic pipe and tubing a | ASTM D2846; ASTM F441; ASTM F442; CSA B137.6 Polypropylene (PP) plastic pipe and tubing a | ASTM F1412 PVDF plastic pipe and tubing a | ASTM F1412 Copper or copper-alloy pipe | ASTM B42; ASTM B302 Copper or copper-alloy tubing (Type K, L, or M) | ASTM B74; ASTM B88; ASTM B251; ASTM B447 Galvanized steel pipe | ASTM A53 a. For secondary water used in process applications only.

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.