§ 18-29-711.1 — Horizontal branch connections above or below vertical stack offsets

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-711.1

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/0ad36ffe-30b3-4bec-8bab-2a185354fdbe

18-29-711.1 Horizontal branch connections above or below vertical stack offsets.

If a horizontal branch connects to the stack within 2 feet (610 mm) above or below a vertical stack offset, and the offset is located more than four branch intervals below the top of the stack, the offset shall be vented in accordance with Section 18-29-915.