§ 42-33 — Liquefied petroleum gases, use inside building
Code of Ordinances of the Town of Cicero, Illinois (Codified through Ordinance No. 71-25, adopted September 23, 2025. (Supp. No. 122)) · Cicero Municipal Code § 42-33
Corpus is an independent public-information project, not the official City of Cicero website. Stable reference: corpuslaw.us/code/48679400-3695-4400-90e2-99d7c379817a
Sec. 42-33. - Liquefied petroleum gases, use inside building.
Containers and first-stage regulating equipment shall be located outside of buildings other than buildings designed of this condition, except containers and regulating equipment utilized indoors under any one of the following conditions: (1) Where temporarily utilized for demonstration purposes and the container has a maximum water capacity of 12 pounds (5kg) (nominal 5 pounds LP - gas capacity); (2) Where utilized with a completely self-contained gas hand torch or similar equipment, and the container has a maximum water capacity of 2.7 pounds (1kg) (nominal 16.8 ounces LP-gas capacity); (3) Where in industrial and temporary applications complying with Section F-2209.2 of this code (BOCA National Fire Prevention Code/1996) and NFPA 58 listed in chapter 44; (4) Where in accordance with the provisions regulating LP - gas systems in buildings or exterior balconies contained in NFPA 58 listed in chapter 44; or (5) Where in storage awaiting use or resale in accordance with Chapter of NFPA 58 listed in chapter 44. Failure to comply with this section shall result in a minimum fine of $150.00 and a maximum fine of $500.00.
(Ord. No. 53-04, § 2, 3-9-2004)