§ 8-248 — Grounding
Code of Ordinances, City of Joliet, Illinois (Supp. No. 201: codified through Ordinance No. 18888, enacted September 1, 2026) · Joliet City Code § 8-248
Corpus is an independent public-information project, not the official City of Joliet website. Stable reference: corpuslaw.us/code/5b72a940-ce38-41ed-b612-4b92dabb4cae
Sec. 8-248. - Grounding.
(a) Grounding all metal conduits, cabinets and other enclosures and the neutral conductor or grounded phase conductor of the service entrance equipment shall be permanently grounded by means of a ground connection. One end of the ground connection (the grounding conductor and its metallic protection) shall be connected by means of an approved ground clamp to a metallic underground water piping system (a grounding electrode) [of the] city or supplying a community well, where such piping system is available. Where an acceptable water piping system is not available, the ground connection shall be connected in accordance with the requirements of the National Electrical Code to a grounding electrode such as: (1) a metal frame of a building, if such building is effectively grounded; or (2) a made grounding electrode, such as a ground rod. (b) The other end of the ground connection shall be connected at the disconnecting means or, in the case of an outdoor made grounding electrode, at the outdoor meter connection device (where such device is installed). If connected at the disconnecting means: (1) the grounding conductor shall be connected to the ground lug (attached to the neutral or grounded phase bus) and the grounding screw or the disconnecting means, and (2) the metallic protection of the grounding conductor, if any, shall be connected to the enclosure for such disconnecting means. If connected to an outdoor meter connection device, the grounding conductor shall be connected to the ground stud of such device and the metallic protection to the enclosure of such device. (c) The neutral conductor or the grounded phase conductor of the service entrance equipment conductors shall be connected to the neutral or grounded phase, bus terminal of the disconnecting means and to the ground stud of the outdoor meter connection device. (d) The size of the conductors used for ground connections and the metallic protection for such conductors shall conform with the requirements of the National Electrical Code. (e) Where the ground connection is connected to an acceptable water piping system, an electrically continuous connection shall be maintained at all times between the ground connection and the water piping system. Where the water is metered, the ground connection shall be connected on the unmetered side of the system if practicable. Where such connection is made on the metered side, a bypass consisting of a conductor of the same size as the grounding conductor and clamps shall be connected around the water meter. Where a portion of the water piping system is either nonmetallic, removable or electrically insulated from another portion of such system by the use of gaskets, such as at a well pump, and such conditions are located between the ground connection and the underground portion of such system, a bypass shall be installed to establish electrical continuity. Metal piping systems that may become energized are required to be bonded in accordance with the 2014 NEC Section 250.104.
(Ord. No. 6554, § 8.13, 10-5-76; Ord. No. 7456, § 3(C), 1-6-81; Ord. No. 17754, § 7, 3-20-18)
Ask a question about Joliet law
Corpus searches the Joliet sections it holds and shows the ones that match, with their citations. Free, no sign-in.