Sec. 3-67. - Conductors for circuits in excess of six hundred volts.

(a) Conductors for circuits operating at a potential in excess of six hundred (600) volts shall be of a type approved for the purpose, suitable for the voltage involved and shall be not smaller than No. 14, and shall, if within a sign or other enclosure, be supported on insulating supports, placed not more than three (3) feet apart, which separate the wires at least two (2) inches from each other and from conducting materials. (b) Conductors within a sign or other enclosure shall have rubber compound or other approved insulation or approved open conductor methods. (c) Sharp bends in the conductors shall be avoided. (d) Conductors, other than installed within a sign, shall be installed in conduit or electrical metallic tubing. Approved insulating bushings shall be used where the gas tube cable enters or leaves the conduit.

(Code 1962, § 21-17)