Sec. 3-72. - Tube terminals entering a box, trough or other enclosure.

Electrode receptacles approved for the purpose shall be used. They shall be of incombustible, nonabsorbent insulating material. A flexible nonconducting seal may be used to close the mouth of the receptacle against the entrance of dust and moisture. The seal shall not be in contact with grounded conducting material. Where physical conditions are such as to make the installation of receptacles impossible, bushings may be used, provided the uninsulated conductor electrode terminals or pigtails and other insulating parts are supported so as to insure a permanent spacing to grounded metal or parts of opposite polarity of not less than one and one-half (1½) inches.

(Code 1962, § 21-17)