§ 5-1111 — International Energy Conservation Code—Section R403.5.3 amended

Code of Ordinances of the City of Lawrence, Kansas (Codified through Ordinance No. 10209, enacted April 14, 2026 (Supp. No. 4)) · Lawrence Code of Ordinances § 5-1111

Corpus is an independent public-information project, not the official City of Lawrence website. Stable reference: corpuslaw.us/code/fca0dfd0-b5f7-4c7b-8217-d25278cb48b4

Sec. 5-1111. - International Energy Conservation Code—Section R403.5.3 amended.

Section R403.5.3 of the 2018 International Energy Conservation Code is hereby amended to read as follows: R403.5.3 Hot water pipe insulation (prescriptive). Insulation for hot water pipe with a minimum thermal resistance (R-value) of R-3 shall be applied to the following: 1. Piping located outside the conditioned space. 2. Piping from the water heater to a distribution manifold. 3. Piping located under a floor slab. 4. Buried in piping. 5. Supply and return piping in recirculation systems other than demand recirculation systems.

(Code 2018, § 5-811)