§ 17.10.040 — Refrigerating unit condensers and cooling jackets
The Code of the City of Wichita, Kansas (Supp. No. 36, Update 1: codified through Ordinance No. 53-088, adopted July 28, 2026) · Wichita City Code § 17.10.040
Corpus is an independent public-information project, not the official City of Wichita website. Stable reference: corpuslaw.us/code/f43ac218-0f22-4836-82a3-559f310291d3
Sec. 17.10.040. - Refrigerating unit condensers and cooling jackets.
(1) That except when potable water provided for a refrigerator condenser or cooling jacket is entirely outside the piping or tank containing a toxic refrigerant, the inlet connection shall be provided with an approved high hazard backflow preventer. Heat exchangers used to heat water for potable purposes shall be of the double wall type. (2) Where a commercial ice machine, which has a refrigerant volume not to exceed two pounds and is water-cooled, a dual check valve with intermediate atmospheric vent may be used as isolation protection of the potable water line. Devices, in excess of the two-pound limit, shall require a reduced pressure principal assembly (RP) backflow prevention device or air gap to protect the potable water.
(Ord. No. 49-403, § 10, 12-11-2012)