Sec. 17.10.160. - Automatic fire suppression systems.
All new installations of automatic fire suppression systems of 30 heads or more, or having a fire department connection, other than dry systems, shall be protected from backflow with an approved double check valve assembly. Any portion of a fire suppression system into which toxic chemicals of any type (corrosion, antibacterial, etc.) are added, shall be individually protected with an approved reduced pressure principle assembly in addition to proper fire service line protection. All piping upstream of the backflow preventer or unprotected fire suppression system shall be of material approved for contact with potable water.
(Ord. No. 49-403, § 22, 12-11-12)