Sec. 5-837. - Protection of objects near boilers.
All wood lath and plaster and other combustible ceilings and beams over and for a minimum distance of four feet on all sides from such boiler and not less than three feet from the top of the boiler to the ceiling shall be shielded with approved metal or other fire-resistive materials. The material to be applied shall leave an air space of not less than one-half inch between the material and the ceilings or beams. The sides as well as the bottom of beams, shall be protected. The distance from the top of the boiler to such shield shall be not less than 12 inches. No combustible partition shall be within three feet of the sides and back and five feet from the front of any boiler, unless such partition shall be covered with fire-resistive material to a height of at least three feet above the floor, and the fire-resistive material shall extend from the end or the back of the boiler to at least four feet in front of it; in which case the distance shall not be less than two feet in front of the sides and four feet from the front of the boiler. If the above requirements for clearance cannot be complied with, when required by the inspector, boiler rooms shall be enclosed with incombustible walls or partitions and ceilings in such manner as may be required by the building code of the city. (Ord. No. 81-65, § 6.2, 11-4-81)
Ask a question about Dearborn law
Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.