Sec. 5-840. - Boiler trimmings - Steam, vacuum and vapor.

Every low pressure steam heating boiler shall be equipped with the following: (1) A safety valve of approved type with lever handle set at 15 pounds and of sufficient size to dissipate all steam which can be generated in the boiler without permitting the pressure in same to exceed 15 pounds per square inch. (2) Water column with try cocks and gauge glass connected directly to the boiler independent of other connections. (3) Steam pressure gauge of approved type with brass syphon loop mounted at top of water column or, if placed more than five feet from water column connection, shall be of approved size. No connections of any kind except water column, blow-down, automatic feeder or low water cutoff connections shall be permitted from steam or water connections from boiler to gauge glass or pressure gauge. (4) A permanent makeup or feed water connection of size approved by the inspector, but in no case smaller than one-half inch, with globe valve placed in same within easy reach of the floor with an approved type check valve between shutoff valve and boiler shall be made to each boiler. (5) Connection not less than one inch in size, equipped with hose end or connected to blow-off piping to permit complete drainage of boiler. (Ord. No. 81-65, § 6.5, 11-4-81)

Ask a question about Dearborn law

Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.