Sec. 5-841. - Same - Water.
Every low pressure hot water heating boiler shall be equipped with the following: (1) Water relief valve of approved make with lever handle, side outlet not less than one inch in size, set to open at 30 pounds per square inch pressure. (2) Altitude gauge of approved make. (3) Thermometer of approved make. (4) Boiler feed connections. A permanent makeup or automatic feed water connection of proper size, but in no case smaller than one-half inch, with globe valve placed in same within reach of floor, shall be made to each boiler. (5) Drain connection shall be not less than three-fourths inches in size, equipped with hose end or connected to blow-off piping to permit complete drainage of boiler. (Ord. No. 81-65, § 6.6, 11-4-81)