For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 5-841 — - Same - Water

Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 5-841

Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/8e6c1d3b-5190-42db-8f33-9c7b227a1d88

Sec. 5-841. - Same - Water.

Every low pressure hot water heating boiler shall be equipped with the following: (1) Water relief valve of approved make with lever handle, side outlet not less than one inch in size, set to open at 30 pounds per square inch pressure. (2) Altitude gauge of approved make. (3) Thermometer of approved make. (4) Boiler feed connections. A permanent makeup or automatic feed water connection of proper size, but in no case smaller than one-half inch, with globe valve placed in same within reach of floor, shall be made to each boiler. (5) Drain connection shall be not less than three-fourths inches in size, equipped with hose end or connected to blow-off piping to permit complete drainage of boiler. (Ord. No. 81-65, § 6.6, 11-4-81)

Ask a question about Dearborn law

Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.