§ 7-951 — International Residential Code amended; Section E3902.2. Garage and accessory building receptacles

Code of Ordinances of the City of Lee's Summit, Missouri (Codified through Ordinance No. 10423, enacted July 14, 2026 (Supp. No. 56)) · Lee's Summit Code of Ordinances § 7-951

Corpus is an independent public-information project, not the official City of Lee's Summit website. Stable reference: corpuslaw.us/code/2bda3076-cff4-4c60-a542-f95897b9222d

Sec. 7-951. - International Residential Code amended; Section E3902.2. Garage and accessory building receptacles.

Section E3902.2 Garage and accessory building receptacles is hereby amended to read as follows: All 125-volt, through 250-volt receptacles installed in garages and grade level portions of unfinished accessory buildings used for storage or work areas and supplied by a single-phase branch circuit rated 150 volts or less to ground shall have ground-fault circuit interrupter protection for personnel. EXCEPTIONS: A. Receptacles that are not readily accessible such as a ceiling mounted receptacle for a garage door opener. B. A single receptacle supplied by a dedicated branch circuit that is located and identified (non GFI) for a specific use by a cord-and-plug-connected appliance such as a refrigerator, freezer or sump pump. C. A receptacle supplying only a permanently installed fire alarm or burglar alarm system.

(Ord. No. 10422, § 1, 7-14-2026)