Sec. 7-953. - International Residential Code amended; Section E3902.11. Indoor damp and wet locations.
Section E3902.11 Indoor damp and wet locations is hereby amended to read as follows: All 125-volt through 250-volt receptacles installed in basements and supplied by a single-phase branch circuit rated 150-volts or less to ground shall have ground fault circuit interrupter protection for personnel. EXCEPTIONS: A. Receptacles that are not readily accessible such as a ceiling mounted receptacle for a garage door opener. B. A single receptacle supplied by a dedicated branch circuit that is located and identified (non GFI) for a specific use by a cord-and-plug-connected appliance such as a refrigerator, freezer or sump pump. C. A receptacle supplying only a permanently installed fire alarm or burglar alarm system.