§ 26-304 — Prevention and elimination of cross connections—Degree of hazard

Code of Ordinances of the City of Jacksonville, North Carolina (Codified through Ordinance No. 2025-52, adopted November 18, 2025 (Supp. No. 63)) · Jacksonville Code of Ordinances § 26-304

Corpus is an independent public-information project, not the official City of Jacksonville website. Stable reference: corpuslaw.us/code/d73fbeb3-f792-434c-bea7-7f59e91c0051

Sec. 26-304. - Prevention and elimination of cross connections—Degree of hazard.

When it is determined that a backflow prevention assembly is required for the protection of the public system, the city shall require the consumer, at his/her own expense, to install an approved backflow prevention assembly at each service connection, to test immediately upon installation. When cross connections are found to exist, the owner, his agent, occupant, or tenant will be notified in writing to disconnect the same within the time limit established by the city. Degree of protection required and maximum time allowed for compliance will be based upon the potential degree of hazard to the public water supply system. The maximum time limits and rules are as follows: (1) Cross connections with private wells or other auxiliary water supplies - immediate disconnection. (2) All facilities which pose a health hazard to the potable water system must have a containment assembly in the form of a reduced pressure principle backflow prevention assembly within sixty (60) days. (3) All industrial and commercial facilities not identified as a "health hazard" shall be considered non-health hazard facilities. All non-health hazard facilities must install, as a minimum containment assembly, a double check valve assembly within ninety (90) days. (4) If, in the judgment of the city, an imminent health hazard exists, water service to the building or premises where a cross connection exists may be terminated unless an air gap is immediately provided, or the cross connection is immediately eliminated. (5) Based upon the recommendation from the city, the consumer is responsible for installing sufficient internal isolation backflow prevention assemblies (reduced pressure principle backflow prevention assemblies or double check valve assemblies) (6) Water mains served by, but not maintained by, the city should be considered cross connections, with the degree of hazard to be determined by the city. The type of protection shall be based upon the degree of hazard, as determined by the city. (7) No person shall fill special tanks or tankers containing pesticides, fertilizers, other toxic chemicals or their residues from the public water system except at a location equipped with an air gap or an approved reduced pressure principle backflow prevention assembly properly installed on the public water supply. (8) All backflow assemblies that are not installed to the specifications set forth in the installation specifications shall be brought to code upon notification. Assemblies previously installed below ground without the proper drain size shall be considered cross connections and should be brought up to date with present standards. (Drain sizes shall be two (2) times the fire service supply or two (2) times the fire service connection. Drain shall follow by gravity to sunlight.) (9) All services outlined by this regulation that do not have containment assemblies installed shall install assemblies by the restrictions outlined. (10) There are no exemptions, or grandfather clauses, which would prohibit the city from requiring the installation of backflow prevention device(s)/assemblies on existing water services when potential hazards are found to exist which endanger the potable water supply.

(Ord. No. 90-03, 2-6-90; Ord. No. 08-29, 6-17-08)

Ask a question about Jacksonville law

Corpus searches the Jacksonville sections it holds and shows the ones that match, with their citations. Free, no sign-in.