20.14.030 Section R403.3.3 Amended; Duct Testing (Mandatory).
Section R403.3.3 of the International Energy Conservation Code is amended to read as follows: R403.3.3 Duct Testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: (1) Rough-in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer’s air handler enclosure if installed at the time of the test. Registers shall be taped or otherwise sealed during the test. (2) Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer’s air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: (1) A duct air-leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. (2) A duct air-leakage test shall not be required for ducts servicing heat or energy recovery ventilators that are not integrated with ducts serving heating or cooling systems. (3) A duct air-leakage test shall not be required for ducts that are sprayed with closed cell foam. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ().
(Ord. 20936 §3; June 29, 2020)
Ask a question about Lincoln law
Corpus searches the Lincoln sections it holds and shows the ones that match, with their citations. Free, no sign-in.