5.10.040 Dry Cleaner Ventilation.
Each dry cleaner or battery of two or more dry cleaners shall be provided with an independent ventilation system which will safely exhaust sufficient air from the dry cleaner interior so as to maintain a minimum air flow of 100 lineal feet per minute face velocity, entering flow, through the loading door whenever the door is open. The duct or discharge stack for this ventilation system shall extend at least five feet above the building roof high point, and shall terminate so as to prevent affluent air from gaining entrance into adjacent buildings, or otherwise so as not to create a health hazard or nuisance; generally, the top of the stack should be above and at least fifty feet from any adjacent building openings accommodating fresh air intake. All ventilation ducts shall be of vapor-proof construction.
(Ord. 15457 §4; March 5, 1990: P.C. §5.56.040: Ord. 7715 §4; May 1, 1962)