5.10.050 Room or Space Ventilation.
(a) Space ventilation shall be provided whereby air will be exhausted from the maintenance room to the outside atmosphere so as to maintain a minimum air flow rate from the customer area through the partition, separating it from the maintenance room, as follows: No. of Dry Cleaners | Min. Air Flow Rate (cfm)/Machine 1-3 | 250 4-8 | 200 9-16 | 150 17 or more | 100 (a) Where grille openings are to be installed in the partition to facilitate air movement, they shall be sized on the basis of 500 cubic feet per min. for each square foot of net grille area and shall be placed as close to the machine as possible. (b) A supply of fresh make-up air equal to or greater than the total volume of air exhausted from the establishment shall be provided so as to eliminate any negative pressures which might otherwise develop within the customer area. (c) The space ventilation as described above shall be provided on a continuous basis while the establishment is open for business, (d) The point of discharge for space ventilation shall meet the same requirements as given for dry cleaner ventilation.
(Ord. 15457 §5; March 5, 1990: P.C. §5.56.050: Ord. 7715 §5; May 1, 1962)