§ 330-15 — Separation of groups on crossarms
Code of Ordinances of the City of Buffalo, New York (Code 2026-03-31: eCode360 publication current through the 2026-03-31 codification (imported 2026-11-12)) · Buffalo City Code § 330-15
Corpus is an independent public-information project, not the official City of Buffalo website. Stable reference: corpuslaw.us/code/044aef5c-a487-407d-a556-5b2a165b4063
§ 330-15: Separation of groups on crossarms.
A. No wires of one group shall be placed on the same crossarm with wires of another group. When Group A and Group B wires, run horizontally from one pole to another, are placed on the same pole, the Group A wires shall occupy the upper position on the pole, and the uppermost crossarm for Group B wires and the uppermost Group B horizontally run cable shall be not less than four feet below the lowest crossarm for Group A wires. B. When Group B and Group C wires, run horizontally from one pole to another, are placed on the same pole, the Group C wires may be placed below the Group B wires, in which case the uppermost Group C crossarm shall be not less than four feet below the lowest crossarm for Group B wires or the lowest horizontally run Group B cable. Where Group C wires are run above Group B wires or other Group B attachments, they shall be placed in accordance with the requirements for Group A wires. C. Horizontally run Group C wires shall always be run below horizontally run Group A wires.