§ 330-19 — Separation of groups on poles
Code of Ordinances of the City of Buffalo, New York (Code 2026-03-31: eCode360 publication current through the 2026-03-31 codification (imported 2026-11-12)) · Buffalo City Code § 330-19
Corpus is an independent public-information project, not the official City of Buffalo website. Stable reference: corpuslaw.us/code/7eaa1255-ca95-4d8e-b8db-7078943ce58e
§ 330-19: Separation of groups on poles.
Group A or Group C wires must not be placed on the same pole with Group B wires unless the voltage does not exceed the following normal operating values: constant-potential metallic circuits: 5,000 volts; alternating-current series circuits: 5,000 volts; direct-current series circuits: 7,000 volts; and direct-current railway circuits: 700 volts, except that, where alternating- or direct-current series circuits do not exceed seven and one-half (7 1/2) amperes, voltage may be increased to 10,000 volts and that all the abovementioned wires shall be covered when installed with at least a standard weatherproof insulation.
Ask a question about Buffalo law
Corpus searches the Buffalo sections it holds and shows the ones that match, with their citations. Free, no sign-in.
