§ 330-19: Separation of groups on poles.

Group A or Group C wires must not be placed on the same pole with Group B wires unless the voltage does not exceed the following normal operating values: constant-potential metallic circuits: 5,000 volts; alternating-current series circuits: 5,000 volts; direct-current series circuits: 7,000 volts; and direct-current railway circuits: 700 volts, except that, where alternating- or direct-current series circuits do not exceed seven and one-half (7 1/2) amperes, voltage may be increased to 10,000 volts and that all the abovementioned wires shall be covered when installed with at least a standard weatherproof insulation.