§ 330-18: Strain insulators.
Each guy attached to a pole on which there are both Group A and Group B attachments or Group B and Group C attachments shall contain a strain insulator, placed not less than six feet from the pole, said distance being measured horizontally. As far as practicable, each strain insulator shall have the following qualifications: A. Mechanical strength equal to the tensile strength of the guy in which it is placed. B. Construction so designed that a rupture of the insulating material shall not result in parting the guy. C. Insulating properties suitable to the voltage of the currents to which the guy is exposed.