§ 131-154 — Inspection
Code of the City of Mount Vernon, New York · Mount Vernon City Code § 131-154
Corpus is an independent public-information project, not the official City of Mount Vernon website. Stable reference: corpuslaw.us/code/3a7d4cb5-bbe6-44cb-93b1-0536c501b21b
§ 131-154: Inspection.
A. No gasoline, diesel or other flammable or combustible motor fuel tank or equipment that has been installed, replaced or relocated may be used until it has been inspected and approved by the Commissioner. B. During such inspection, all tanks and piping shall be tested by a minimum air or hydrostatic pressure of 10 pounds per square inch or as prescribed by the manufacturer. Such pressure shall be maintained for a period of at least 30 minutes, during which time, if the test is by air pressure, the entire exterior surface and all joints shall be coated with a solution of soap and water or other material suitable for the purpose which will indicate the presence of leaks. Hydrostatic pressure, if used, shall be gauged in the top of the tank, and the tank and piping shall be inspected for the presence of liquid to indicate leaks. Any leakage detected by any of the methods described shall be deemed evidence of failure to maintain the requirements of the specifications. Under no circumstances shall bottled gases under pressure be used.
Ask a question about Mount Vernon law
Corpus searches the Mount Vernon sections it holds and shows the ones that match, with their citations. Free, no sign-in.