§ 131-155: Storage.

A. Storage of gasoline, diesel and other flammable or combustible liquid motor fuel shall be in compliance with Parts 1164 and 1171 of Chapter C of the New York State Uniform Fire Prevention and Building Code and with National Fire Prevention Association 30A-87, Automotive and Marine Service Station Code. B. In addition, all new and existing tanks for the storage of more than 2,000 gallons of gasoline, diesel or other flammable or combustible motor fuel must be equipped with a constant monitoring electronic leak-detecting system that gives visual and audible warning signals and must be of a type approved by the Commissioner.