§ 131-244: Refrigerating machinery rooms.
A. Open flames and electrical equipment. In a refrigerating machinery room for Class A or B system using a flammable refrigerant, a hydrocarbon or a substituted hydrocarbon, no fire, flame or arc light will be permitted and no major electrical equipment except motors and switchboard to operate refrigerating machinery will be permitted. All starting equipment, including switches, automatic starters and the like, must be of the oil-immersed or -enclosed type. An emergency switch controlling all the electrically operated refrigerating machinery for all type refrigerants shall be located outside the refrigerating machinery room where it can be readily reached and operated in case of emergency. B. Ventilation. (1) Each Class A, B or C refrigerating machinery room of any system shall be independently provided with means for adequate ventilation to the outer air. The ventilation shall consist of a window or windows opening directly to the open air or of mechanical means capable of exhausting the foul air from the room. (2) When a window or windows are used, if placed in opposite walls so as to provide a through-air circulation to the outer air, a total area of inlet and outlet, respectively, of not less than that specified in column D of the table hereinafter set forth in this section shall be provided. When a window or windows are placed in one wall, a total area shall be provided of not less than that specified in column E of said table. (3) When mechanical means are used, they shall consist of driven exhaust fan of the enclosed, cased blower type which shall be capable of removing from the refrigerating machinery room the amount of air specified in column B of the table. The inlet to the fan shall be located near the refrigerating equipment. The outlet from the fan shall terminate not less than six feet above the sidewalk and in no case under a stairway or fire escape. Where air ducts are used on either the inlet or discharge side of the fan, they shall each have an area of not less than that specified in column C. Sharp bends in the run of the ducts shall be avoided. The control for such mechanical means of ventilation shall be easily accessible and located outside the refrigerating machinery room. (Door openings leading directly to the open air shall be considered equivalent to windows for the requirements specified in columns D and E.) (4) Where a nonirritant and nonflammable refrigerant is employed, the requirements as given in column D of the table may be reduced by 1/2. When air or water is employed as the refrigerant, no ventilation shall be required. (5) In addition to mechanical means of ventilation in refrigerating machinery room or rooms where a Class A system or Class B system using ammonia is installed, a water deluge may be provided, which shall consist of a sprinkler system having open heads of not less than one-fourth-inch orifice spaced not more than eight feet apart in any direction, and such system shall be located above all the refrigerating apparatus and piping in the refrigerating machinery room. Not more than one head shall be installed on a three fourths-inch pipe, five heads on a one-inch pipe, six heads on a one-and-one-fourth inch pipe. The deluge system shall be permanently connected with the main house supply or other assured source from which a constant water pressure of not less than 20 pounds per square inch can be maintained on the inlet side of the main control valve or valves at all times. The control valve or valves for such water deluge system shall be manually operated, easily accessible and shall be labeled and located outside the refrigerating machinery room. A | B | C | D | E Refrigerant in System(pounds) | Mechanical Discharge(cubic feet per minute) | Mechanical Duct Area(square feet) | Window Area for Each Opposite Side(square feet) | Window Area for 1 Side Only(square feet) Up to 20 | 150 | 1/4 | 1 | 6 50 | 250 | 1/3 | 1 1/2 | 12 100 | 400 | 1/2 | 2 | 16 150 | 550 | 2/3 | 2 1/2 | 19 200 | 680 | 2/3 | 3 | 25 250 | 800 | 1 | 3 1/2 | 29 300 | 900 | 1 | 4 | 32 400 | 1,100 | 1 1/4 | 4 1/2 | 38 500 | 1,275 | 1 1/4 | 5 | 42 600 | 1,450 | 1 1/2 | 6 | 45 700 | 1,630 | 1 1/2 | 6 1/2 | 48 800 | 1,800 | 2 | 7 | 51 900 | 1,950 | 2 | 7 1/2 | 55 1,000 | 2,050 | 2 | 8 | 59 1,250 | 2,350 | 2 1/4 | 9 | 68 1,500 | 2,800 | 2 1/4 | 11 | 78 1,750 | 3,150 | 3 | 12 1/2 | 87 2,000 | 3,500 | 3 1/2 | 14 | 98 2,500 | 4,150 | 4 | 16 | 113 3,000 | 4,500 | 4 1/2 | 18 | 130 4,000 | 6,000 | 6 | 24 | 167 5,000 | 7,500 | 7 1/2 | 30 | 204 6,000 | 9,000 | 9 | 36 | 241 7,000 | 10,500 | 10 1/2 | 42 | 278 8,000 | 12,000 | 12 | 48 | 315 9,000 | 13,000 | 13 | 52 | 342 10,000 | 14,000 | 14 | 56 | 360 12,000 | 17,000 | 17 | 68 | 425 14,000 | 19,000 | 19 | 75 | 470 16,000 | 22,000 | 22 | 86 | 540 18,000 | 24,000 | 24 | 92 | 580 20,000 | 26,500 | 26 | 100 | 630 25,000 | 33,000 | 33 | 121 | 760 30,000 | 39,000 | 39 | 142 | 870 35,000 | 44,000 | 44 | 155 | 940 40,000 | 51,000 | 51 | 176 | 1,060 45,000 | 56,000 | 56 | 190 | 1,120 C. Indirect method. (1) In Class A and B systems where the indirect method of refrigeration is permitted, the refrigerating machinery room shall be constructed according to the following requirements: Where an irritant refrigerant is used, the refrigerating machinery room shall be maintained vaportight, except that all doors opening to other parts of the building shall be self-closing and so close fitting as to prevent the passage of vapor and shall be kept closed at all times except during entrance and exit. All doors shall open outward. All other openings that may permit the passage of vapor to other parts of the building shall be vaportight and kept closed. There shall be no openings to elevator shafts, but openings to dumbwaiter shafts shall be permitted, provided the openings are protected with self-closing and close-fitting fire doors. There shall be adequate ventilation to the outside as required under Subsection B of this section. (2) In Class C systems of the remote type, the pressure-imposing element, condenser, receiver or shell-type apparatus need not be located in a separate machinery room but shall be located at least 10 feet from storage of combustible materials in an accessible part of the building with adequate lighting facilities, and they shall be protected against mechanical injury by a metal netting partition arranged with a door and shall not be located under stairways nor near dumbwaiter shafts not equipped with self-closing or close-fitting doors nor near elevator shafts.
Ask a question about Mount Vernon law
Corpus searches the Mount Vernon sections it holds and shows the ones that match, with their citations. Free, no sign-in.