pt. 2 — Smoke Purge System Design Parameters
Municipal Code of the City of White Plains, New York (Codified through Ordinance of October 5, 2026. (Supp. No. 79, Update 2)) · White Plains Supplemental Building and Fire Codes ch. 6, pt. 2
Corpus is an independent public-information project, not the official City of White Plains website. Stable reference: corpuslaw.us/code/3c5e8f0b-3dc4-4b3c-9c68-4338a5b9b052
Part 2. - Smoke Purge System Design Parameters
a. Smoke purge system ducts, transfers, etc. passing through firerated partitions shall be protected as follows: (1) One Hour rated wall or ceiling. (i) Do not provide a fire or smoke damper at wall penetration. (ii) Sprinkler head(s) are to be installed on fire load side of wall(s), at return air transfer openings. (2) Two hour rated wall or ceiling. (i) Provide automatic combination fire/smoke damper with manual control override. (ii) Activation - Heat link closes damper. The damper shall be UL555S classified with low (285°F) and high limit (450°F) temperature stats and open/closed status switches. Dampers maybe electrically or pneumatically operated. The damper shall be no smaller than 16 square inches. b. Conduit for Smoke Purge Control (1) Control wiring shall be run in metal conduit. (rigid or EMT). (2) Pneumatic tubing must be copper. c. Ducts through Exitways and Within Rated Ceiling Assemblies. (1) Smoke purge system supply and exhaust ducts passing through a rated exitway or within a fire-rated suspended ceiling assembly shall be wrapped with thermal fiber - two hours or encased in a two-hour rated enclosure. (2) Trapeze hangers to be outside of thermal wrapping. d. Smoke Purge Fans. (1) Smoke Purge System fans must provide for a minimum of six air changes per hour (or greater if necessary), to obtain adequate visibility within legal means of egress within ten minutes of starting smoke purge. (Adequate visibility is interpreted as clear enough to see exit signs to permit a person to safely exit the building). (2) The smoke purge fan system may be designed as either a separate fan system or as an integrated smoke purge /HVAC system, and as required by Section 4 (Building Alterations and Additions). (3) All smoke purge fans (supply and return) and controls (including air compressors) shall be connected to the building emergency or standby generator and adequate electric power provided for same. If no emergency or standby power source is existing a new emergency or standby source shall be established to power the purge system for no less than 90 minutes upon loss of normal power. (4) Manual override switches shall be provided at the fire alarm panel or fire command station panel to control both smoke purge supply and smoke purge exhaust fans separately. Refer to Part 3 for more information. e. Duct Work. (1) All smoke purge system ducts shall be galvanized steel with minimum thickness of 22 ga. constructed in accordance with ASHRAE and SMACNA sheetmetal ductwork construction details. Flexible ductwork is not permitted in duct systems that are part of a smoke purge system (return or exhaust ductwork). Flexible duct is permitted at supply diffuser connections and at air handling equipment for vibration isolation (maximum three ft. length). (2) Design and spacing of duct hangers shall be in accordance with SMACNA duct construction details but hangers to be minimum of 20 ga. steel and be of the trapeze type. (3) Where a smoke purge enters a rated shaft, utilized as a smoke exhaust riser, N.F.P.A. requirements for a vertical boot shall be followed (22-inch height, directed upward within the shaft itself), or in lieu of such boot, automatic combination fire/smoke dampers shall be provided at such core shafts. Smoke dampers shall be operated either pneumatically or electrically as previously described in this Part. (4) All smoke purge system components (including ductwork) shall be clearly identified as such by stenciling the function and zone on the components, e.g. Smoke Purge Supply - Zone 2; Smoke Purge Exhaust - Zone 3; Smoke Damper No. 5; etc. Stenciling shall be 6" high red letters located (every ten feet along duct). f. Smoke Purge Coverage. (1) Smoke purge systems shall be designed for a minimum of one zone per floor. (2) All areas of a building or space shall be capable of being purged except as follows: (i) Dwelling units; (ii) Hotel Guest rooms; (iii) Electrical closets, telephone closets, or storage rooms, 75 square feet in size or less. g. Smoke Exhaust of Interior Stairwells. (1) All new interior exitway stairways shall be equipped with an approved automatic smoke-actuated roof scuttle vent, or other approved automatic smoke purge system located at the uppermost ceiling thereof. Such system shall activate the building fire alarm system. This provision shall not conflict with stair pressurization provisions of the State of New York codes.
Ask a question about White Plains law
Corpus searches the White Plains sections it holds and shows the ones that match, with their citations. Free, no sign-in.