Part 4. - Smoke Purge System Test
(1) Upon completion of system installations, the mechanical design engineer of record shall personally conduct, and oversee, for verification purpose, a field smoke purge test (in the presence of the City of White Plains Code Enforcement Officer and Fire Prevention Bureau representative). (2) Such tests shall be conducted under both normal and emergency power conditions. (3) Any and all necessary modification and system reinforcements (such as boosters, fans, ducts, etc.) shall be provided if smoke purge tests result in unsatisfactory performance. (4) Testing Criteria-Smoke shall be evacuated to such a degree that exit signs shall be clearly visible from a distance of 50 feet within ten minutes of the commencement.