pt. 3 — Sequence of Operation and Control Functions

Municipal Code of the City of White Plains, New York (Codified through Ordinance of October 5, 2026. (Supp. No. 79, Update 2)) · White Plains Supplemental Building and Fire Codes ch. 6, pt. 3

Corpus is an independent public-information project, not the official City of White Plains website. Stable reference: corpuslaw.us/code/d3ea0d5e-49b8-4328-854e-9cddeeee6d79

Part 3. - Sequence of Operation and Control Functions

a. Sequence of Operation. (1) The activation of one automatic initiation device (e.g. smoke detector) or pullstation shall cause the central fire alarm system to go into alarm activation in accordance with the sequence required for the particular existing building. (Note: If a new building or new fire alarm system contact Fire Prevention Bureau for required sequence of operation). In addition, any combination fire/smoke dampers on the floor in alarm shall close. If the low limit temperature firestat (285°F) activates the combination fire/smoke dampers shall close. (2) The simultaneous activation of any two automatic initiation devices (e.g. smoke detectors) or one heat detector or the activation of a single waterflow switch shall cause the central fire alarm system to go into alarm activation in accordance with the sequence of operation required for the particular existing building. (Note: If a new building or new fire alarm system contact Fire Prevention Bureau for required sequence of operation). In addition, the smoke purge system shall automatically initiate and the following shall occur: (i) Index all smoke dampers on the particular floor in alarm to an "open" position (supply and return) and index all other building smoke dampers (supply and return) to a "closed" position. (ii) Index supply air handling unit(s) air handling (unit(s) or fans) to 100 percent outside air and return air handling unit(s) or fans to 100 percent spill. The return damper (between the supply and return systems) shall be fully closed. Note: The return dampers within the air handling units that are part of a smoke purge system shall be a UL smoke damper. The smoke purge system shall override the low limit temperature sensor on the fire smoke damper if it was activated. If the high limit temperature firestat (450°) is activated during the purge process the fire/smoke damper shall close permanently and smoke purge will be halted. b. Control Functions: (1) Purge manual control shall be provided at the fire alarm panel or fire command station in the main lobby. This control shall consist of the following: (i) A switch shall be provided for each floor or area that is part of the smoke purge system. The switch shall have three positions "on" "off" and "automatic". (ii) The switch when indexed to the "on" position shall: I. Index all smoke dampers on the particular floor to an open position (supply and return) and index all other building smoke dampers (supply and return) to a "closed" position. II. Index the appropriate supply air handling unit(s)or fans to 100 percent outside air and the appropriate return air handling unit(s) or fans to 100 percent spill. The return damper (between the supply and return systems) shall be fully closed. Note: The return dampers within the air handling units that are part of a smoke purge system shall be a UL smoke damper. Note: The smoke control system ductwork and components shall be designed and configured to accommodate excessive static pressure that may occur during purge cycle. (iii) The switch when indexed to the "off" position shall: I. Index all smoke dampers on the particular floor or zone to "closed" position (supply and return). II. Index the appropriate supply and return air handling units or fans to their normal mode of operation. Note: The smoke control system ductwork and components shall be designed and configured to accommodate excessive ductwork static pressure that may occur during purge cycle. (iv) The switch when indexed to the "automatic" position shall: I. Cause the smoke purge system to be controlled automatically via the fire alarm system. Alarm initiation devices shall cause the purge system to automatically activate. During non-alarm conditions the H.V.A.C. systems and fire/smoke dampers that are part of the smoke purge system can be controlled by a building management or similar control system( if one exists) as long as the fire alarm system has override priority. The control switches shall not be able to override the fire/smoke damper if the high limit temperature (450°) is activated.

Ask a question about White Plains law

Corpus searches the White Plains sections it holds and shows the ones that match, with their citations. Free, no sign-in.